Exeltech KC SNMP MIB reference

Exeltech Software Downloads · Download KCSNMPV2.mib

KCSNMPV2.mib describes what the monitor card of an Exeltech KC power system reports over SNMP, and the settings an SNMP manager can change. This page lists every object and trap in it, with its full OID, and what to watch for.

Item Value
Module EXELTECH-MIB
File KCSNMPV2.mib (dated 29 July 2024)
Enterprise 1.3.6.1.4.1.30320 (Exeltech)
Objects 1.3.6.1.4.1.30320.2.0, below called …
Format SMIv1 objects (OBJECT-TYPE) and SNMPv1 traps (TRAP-TYPE)

Using the MIB

Objects

Battery: ….1

OID Name Access Meaning
….1.1 batDCV read-only Battery voltage, in tenths of a volt: divide by 10
….1.2 batDCI read-only Battery current, A
….1.3 batABUS read-only A bus DC voltage, V, if the system has one
….1.4 batBBUS read-only B bus DC voltage, V, if the system has one

Phases 1 to 3: ….2, ….3, ….4

Each phase has the same eight objects: phase 1 under ….2, phase 2 under ….3, phase 3 under ….4. In the names, n is the phase number.

OID (phase 1) Name Access The MIB's description
….2.1 utilityAcvLn read-only Inverter AC voltage, V. See known issue 1
….2.2 utilityAciLn read-only Inverter current, A. See known issue 1
….2.3 utilityFrqLn read-only Inverter frequency, Hz. See known issue 1
….2.4 inverterAcvLn read-only Utility AC voltage, V. See known issue 1
….2.5 inverterAciLn read-only Utility current, A. See known issue 1
….2.6 inverterFrqLn read-only Utility frequency, Hz. See known issue 1
….2.7 line1AcvOut, line2ACVOut, line3ACVOut read-only Output voltage, V
….2.8 temperatureSTSLn read-only SCR (transfer switch) temperature, °C

Alarms: ….5

OID Name Access Meaning
….5.1 systemAlarms read-only The conditions present now, one bit each: see the bits
….5.2 slotAlarms read-only Module slots not communicating: bit 0 (0x001) is slot 1, up to bit 10 (0x400), slot 11
….5.3 alarmOne read-only Alarm 1, the minor alarm: 1 when a condition configured for Alarm 1 is present, else 0
….5.4 alarmTwo read-only Alarm 2, the major alarm: 1 when a condition configured for Alarm 2 is present, else 0

The bits of systemAlarms

Bits 0 to 15 are the power system's conditions, and bits 16 to 31 the transfer switch's. The last column is the name StatusBoost and the Alarm Configuration Tool show for the same condition, where they show one.

Bit Mask The MIB's text In StatusBoost
0 0x00000001 Low DC Volt Alarm Module Low DCV Detected
1 0x00000002 Power Module Fail Module Overload Detected (see known issue 3)
2 0x00000004 NA
3 0x00000008 PowerLvlIndicator Module Marginal Load Level Detected
4 0x00000010 Module Temperature Warning Module Temp Warning Detected
5 0x00000020 Module Local Disable Module Offline Detected (see known issue 3)
6 0x00000040 cage comm failure detected Inverter System Cage Comm Degraded
7 0x00000080 AB Bus Fail Detect Inverter System AB Bus Fault Detected
8 0x00000100 System Disable Inverter System Offline Detected
9 0x00000200 Power Module fail detected Module Fault Detected
10 0x00000400 Slot Not Detected fault Module Not Detected
11 0x00000800 Ph1 on Ref2 Phase 1 on Reference 2
12 0x00001000 Ph1 on Ref2 (see known issue 2) Phase 2 on Reference 2
13 0x00002000 Ph1 on Ref2 (see known issue 2) Phase 3 on Reference 2
14 0x00004000 NA Cage Not Detected (see known issue 3)
15 0x00008000 NA
16 0x00010000 Utility Primary Utility Primary
17 0x00020000 Inverter source fault Bad Inverter Source
18 0x00040000 Utility source fault Bad Utility Source
19 0x00080000 MBS Lockout Asserted MBS Lockout Asserted
20 0x00100000 Sources not sync Sources Not Sync'd
21 0x00200000 Fan fault detect STS PowerSwitch PowerSwitch Fan Fault Detected
22 0x00400000 Warm Temp STS PowerSwitch PowerSwitch Warm Temp
23 0x00800000 Overtemp STS PowerSwitch PowerSwitch Over Temp
24 0x01000000 SCR Active (Legacy)
25 0x02000000 Utility SCR Driving PowerSwitch Utility Source Engaged
26 0x04000000 STS Backfeed protection enabled STS Backfeed Protection Engaged
27 0x08000000 Line 2 Line fail Line to Line Fault Detected
28 0x10000000 STS Forced Inverter State Forced Inverter State Detected
29 0x20000000 STS Forced Utility State Forced Utility State Detected
30 0x40000000 STS Forced Contactor Open Forced Contactor Open
31 0x80000000 STS Contactor Open Detected Contactor Open Detected

Settings: ….6

OID Name Access Meaning
….6.1 dCVLow read-write Low battery voltage limit for lowDCtrap, in tenths of a volt: multiply the voltage by 10
….6.2 dCVHigh read-write High battery voltage limit for highDCtrap, in tenths of a volt
….6.3 alarm1Configuration read-only Which systemAlarms bits raise Alarm 1, as a mask of the same bits. The MIB says to change it with ProductStatus; today that is StatusBoost's System Configuration or the Alarm Configuration Tool
….6.4 alarm2Configuration read-only Which systemAlarms bits raise Alarm 2, the same way
….6.5 slotConfiguration read-only Which module slots are configured, one bit each as in slotAlarms
….6.6 trap-target-ip1 read-write IP address of the first trap manager. 0.0.0.0 stops all traps
….6.7 trap-target-ip2 read-write IP address of the second trap manager; 0.0.0.0 removes it
….6.8 trap-target-ip3 read-write IP address of the third trap manager; 0.0.0.0 removes it
….6.9 ipAddressStatic read-write The static IP address
….6.10 subnetMaskStatic read-write The static subnet mask
….6.11 defaultGatewayStatic read-write The static default gateway
….6.12 setNetworkConfig read-write Network options, one bit each: 0x01 DHCP or 0x02 static address, 0x04 SNMP, 0x08 SNTP, 0x10 web server. Writing it restarts the network card; clearing 0x04 turns off SNMP
….6.13 ntp-ip1 read-write IP address of the SNTP server
….6.14 ntp-set read-write The time zone for SNTP. Set it with StatusBoost's Network Feature Setup
….6.15 traps-config read-write The all-good trap: one every 30 s × the value (0 to 255); 0 turns it off
….6.16 logging-config read-write Factory use only

System and modules: ….7

OID Name Access Meaning
….7.1 systemName read-write The system's part number, from its barcode
….7.2 systemSerial read-write The system's serial number
….7.3 monitorName read-only The monitor card's part number, from its barcode
….7.4 monitorSer read-only The monitor card's serial number
….7.5 to ….7.70 slot1Name … slot11Out read-only Six objects for each module slot, 1 to 11 (below)

The systemName and systemSerial are set at the factory.

Slot s (1 to 11) starts at ….7.(6s − 1): slot 1 at ….7.5, slot 2 at ….7.11, up to slot 11 at ….7.65. From there:

OID (slot 1) Name Meaning
….7.5 slotsName The module's part number, from its barcode
….7.6 slotsSer The module's serial number
….7.7 slotsFan The module's fan speed
….7.8 slotsTemp The module's temperature
….7.9 slotsSt The module's status bits
….7.10 slotsOut The module's output level

In the names, s is the slot number, for example slot7Temp at ….7.44.

Traps

The traps are SNMPv1 traps. A manager that receives them as SNMPv2 notifications sees the trap OID enterprise.0.number (RFC 3584), shown in the last column.

Trap Enterprise Number Variables When SNMPv2 trap OID
lowDCtrap batDCV (….1.1) 1 batDCV, dCVLow The battery voltage fell below the low limit ….1.1.0.1
highDCtrap batDCV (….1.1) 2 batDCV, dCVHigh The battery voltage rose above the high limit ….1.1.0.2
alarmConfig1trap alarms (….5) 3 alarm1Configuration, systemAlarms Alarm 1, the minor alarm, was raised ….5.0.3
alarmConfig2trap alarms (….5) 4 alarm2Configuration, systemAlarms Alarm 2, the major alarm, was raised ….5.0.4
generalAlarmtrap alarms (….5) 5 alarmOne, alarmTwo A general status update ….5.0.5
slotAlarmtrap alarms (….5) 6 slotAlarms A module slot status update (see known issue 4) ….5.0.6

Known issues

  1. Utility or inverter: the phase objects' names and descriptions disagree. Objects 1 to 3 of each phase are named utility…, but described as inverter values; objects 4 to 6 are named inverter…, but described as utility values. Which is right is being checked. Until then, compare a reading with what StatusBoost shows before relying on it.
  2. Bits 11, 12 and 13 of systemAlarms all read "Ph1 on Ref2" in the MIB. They are phase 1, phase 2 and phase 3 on Reference 2.
  3. Bits 1, 5 and 14 of systemAlarms have different names in the MIB and in StatusBoost: "Power Module Fail" and Module Overload Detected; "Module Local Disable" and Module Offline Detected; "NA" and Cage Not Detected. The table above shows both.
  4. slotAlarmtrap has the same description as generalAlarmtrap, "A general Status update". It carries slotAlarms, so it reports the module slots.
  5. The bit masks are signed. systemAlarms and the configuration objects are INTEGER, a signed 32-bit number, so a manager shows a value with bit 31 (Contactor Open Detected) set as negative. Read them as unsigned 32-bit numbers.

These are notes about the MIB's text. The MIB file is published as it is, so the object names and OIDs that managers already use stay the same.